BFP Efficiency Calculator

Measure the real-world efficiency of a boiler feed pump from field data: flow, differential pressure and shaft power.

Inputs

Discharge − suction pressure at the pump flanges.

Water at 220°F ≈ 0.95; ambient water = 1.00.

Results

Total dynamic head486.32ft
Hydraulic power11.67HP
Hydraulic power (metric)8.70kW
Shaft (brake) power37.01HP
Overall pump efficiency31.5%
AssessmentVery poor — pump likely worn or badly off-BEP.
Ad slot (calc-inline-1) — configure AdSense in Admin → Settings

Formula

η_pump = (Q × H × SG / 3960) / Brake HP, where Brake HP = Motor kW × η_motor / 0.7457.

Worked example

A BFP moving 100 GPM at 200 psi ΔP with 220°F water (SG 0.95) drawing 30 kW at a 92% motor: TDH ≈ 486 ft, hydraulic HP ≈ 11.7, shaft HP ≈ 37, efficiency ≈ 32% — a strong sign of wear or oversizing.

Frequently asked questions

What is a typical BFP efficiency?

New multistage BFPs run 65–75%. Field values of 50–60% are common after a few years. Below 45% usually justifies overhaul.

Why is my efficiency so low?

Most likely causes: worn wear rings, operating far from BEP (throttled discharge), or oversizing at design.

Should I use nameplate motor efficiency?

No — use the operating-point value. Motors run inefficiently below 50% load.